3 Stage Electric Reheat – With Dead Band

iCOM Control Training and Service Manual

3 Stage Electric Reheat – With Dead Band

Temp Set Point - (1/2 Dead Band + 1/2 Proportional Band)

Temp Set Point: 70°F

 

 

 

 

Proportional Band: 8°F

Reheat 1 On

 

 

Dead Band: 2°F

 

 

 

Reheat 2 On

 

 

 

 

 

 

 

Reheat 3 On

 

 

 

 

65

66

67

68

69

70

 

 

 

Reheat

DB

 

 

Reheat

 

 

 

 

 

2 Off

Reheat

 

 

3 Off

 

 

 

 

 

 

 

 

 

 

1 Off

 

Decreasing Temperature

 

 

 

 

Note: in the above example that the control band begins at the 70°F temperature set point and has a length of 5°F, which is ½ of the programmed temperature dead band value plus ½ of the programmed temperature proportional band value.

As the return air temperature decreases Reheat 1 is activated at 67.7°F or ½ of the dead band value plus 33% of the heating control band. If the return air temperature continues to decrease Reheat 2 will activate at 66.4°F or ½ of the dead band value plus 66% of the heating control band. If the return air temperature continues to decrease Reheat 3 will activate at 65°F or ½ of the dead band value plus 100% of the heating control band.

When the return air temperature starts to increase, Reheat 3 is deactivated at 66.4°F or ½ of the dead band value plus 66% of the heating control band. Reheat 2 is deactivated at 67.7°F or ½ of the dead band value plus 33% of the heating control band. Reheat 1 is deactivated at 69°F or ½ of the dead band value plus 0% of the heating control band.

Remember the temperature dead band value is used by the control to shift the cooling on/ off operations away from the temperature set point.