Example: Display: 192.168.254.001

iCOM Control Training and Service Manual

6.Each set of unit control boards must be set up individually, then connected to the network switch and checked before the next board can be setup

6a. Large Displays and Control Boards must each be programmed with a different IP Address.

Example: Display: 192.168.254.001

Example: Control Board: 192.168.254.010

6b. Each Display and Control Board in the iCOM network must have the same Gateway IP address.

Example: Gateway IP: 192.168.254.75

6c. Each Display and Control Board in the iCOM network must have the same Netmask IP address.

Example: Netmask IP = 255.255.255.000

6d. The Unit to Unit (U2U) address must be programmed in the necessary order for setup.

Example: Unit Display: 33 – 64 and Unit Control Board: 1 - 32

43

Page 44
Image 44
Liebert TM-10098 service manual iCOM Control Training and Service Manual, Example: Display: Example: Control Board