Dual Cooling at 100% Capacity – No Dead Band

iCOM Control Training and Service Manual

2-Stage or 4-Stage control method. If the chilled water temperature is not cold enough the valve control band is replaced by the compressor band.

Dual Cooling at 100% Capacity – No Dead Band

Temp Set Point + (1/2 Proportional Band + 1/2 Proportional Band)

Temp Set Point: 70°

 

 

 

 

 

 

 

Proportional Band: 8°

 

 

 

 

 

 

 

 

 

 

 

100%

Cool 1 On

Cool 2 On

 

 

 

 

 

Open

 

 

 

Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Closed

 

 

 

 

 

 

 

 

70

71

72

73

74

75

76

77

78

79

 

Band 1 Chilled Water

Band 2 Compressors

 

 

 

Valvel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increasing Temperature

An addition program available with the Dual Cooling option is called Minimum Chilled Water Temperature. This program allows the end user to select the minimum chilled water temperature that permits simultaneous operation of the chilled water control and compressor control. When the supply chilled water temperature decreases to this programmed value ONLY the chilled water valve control is operational, the compressors are locked out.

Staged Electric Reheat

The basic temperature heating control band is established at the temperature set point with the length equal to ½ of the programmed temperature proportional band divided by the number of reheat stages.

The Liebert DS units are supplied with three (3) reheat stages (elements), each stage is rated at 1/3 of the unit capacity. The three (3) stages will operate in an on/ off configuration to reheat the unit discharge air as it enters the space.

The temperature controller activates the first electric heating stage when the return air temperature decreases to 33% of the heating proportional band. The second electric heating stage activates when the return air temperature decreases to 66%

21

Page 22
Image 22
Liebert TM-10098 service manual Dual Cooling at 100% Capacity – No Dead Band, Staged Electric Reheat