Liebert TM-10098 service manual iCOM Diagnostics / Service Mode Program

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 124
Image 124
iCOM Diagnostics / Service Mode Program

iCOM Control Training and Service Manual

iCOM Diagnostics / Service Mode Program

The iCOM controller has a valuable tool built into software under the SERVICE MENU. This program allows the user to evacuate and charge the refrigerant circuit at installation, turn on/off all loads (outputs) for testing, and allows user to check all inputs.

The procedure is as follows:

1- From the main screen select the SERVICE MENU parameters. 2- In the SERVICE MENU screen select the SERVICE icon.

3- Enter password and scroll to MANUAL MODE, select YES with the up key. 4- Now scroll to Fan On and select ON with the up key. The fan must be on to operate loads in this mode. You must turn off the fan and service mode when completed.

The Compressor 1 and 2 selections are for the ON/OFF and RUN, EVACUATE, and CHARGE modes.

When user scrolls to the Compressor 1 or 2 positions in the parameters list he must press enter to select the first item. Enter again will move the cursor to the ON/OFF selection first (far right item) then using the up arrow key the compressor may be turn on and down key will turn off. Now with the cursor on the ON/OFF position, now use the right arrow key to select the RUN, EVACUATE, CHARGE function and the up or down arrow key to make changes. The RUN selection is the normal operating position.

Parameters list is found on pages in Chapter 2

123

Page 124
Image 124
Liebert TM-10098 service manual iCOM Diagnostics / Service Mode Program, iCOM Control Training and Service Manual