HUM HRS

iCOM Controls Training and Service Manual

028

HUM HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

the fan are higher than

 

 

 

 

 

 

the threshold set.

 

 

 

 

029

SUPPLY

sensor faulty or not

Warning

no

no

-

 

SENSOR

present, but needed from

 

 

 

 

 

FAILURE

control (supply limit

 

 

 

 

 

 

control enabled).

 

 

 

 

031

ROOM

no valid data from the

Alarm

yes

yes

no

 

SENSOR

std. sensor

 

 

 

 

 

FAILURE

 

 

 

 

 

032

SENSOR A

no valid data from sensor

Warning

no

no

-

 

FAILURE

A

 

 

 

 

034

NETWORK

the unit showing this

Warning

no

no

-

 

FAILURE

event has no connection

 

 

 

 

 

 

to the unit #1.

 

 

 

 

036

UNIT ON

fan motor in operation

Message

-

-

-

037

UNIT OFF

unit shut down

Message

-

-

-

038

SLEEP MODE

unit is in sleep mode:

Message

-

-

-

 

 

according to the settings

 

 

 

 

 

 

it is switched off or

 

 

 

 

 

 

working with a selectable

 

 

 

 

 

 

deadband.

 

 

 

 

039

STANDBY

unit is in standby (fan

Message

-

-

-

 

MODE

off), waiting for a call to

 

 

 

 

 

 

start from the system (if

 

 

 

 

 

 

a unit fails or there is a

 

 

 

 

 

 

bus interruption).

 

 

 

 

040

POWER ON

control is powered again

Message

-

-

-

 

 

after a power off.

 

 

 

 

041

POWER OFF

no power to the control:

Message

-

-

-

 

 

this message will appear

 

 

 

 

 

 

at the next power on.

 

 

 

 

042

Unit 1

this event is created from

Warning

no

no

-

 

disconnected

a coldfire display only:

 

 

 

 

 

 

the display doesn't find

 

 

 

 

 

 

unit #1

 

 

 

 

043

Unit 2

"

Warning

no

no

-

 

disconnected

 

 

 

 

 

044

Unit 3

"

Warning

no

no

-

 

disconnected

 

 

 

 

 

045

Unit 4

"

Warning

no

no

-

 

disconnected

 

 

 

 

 

046

Unit 5

"

Warning

no

no

-

 

disconnected

 

 

 

 

 

047

Unit 6

"

Warning

no

no

-

 

disconnected

 

 

 

 

 

94