P38: Smoke Detector

iCOM Control Training and Service Manual

P38: Smoke Detector

 

 

 

 

P38-1:

24 VAC Out SDC)

P38-3:

24 VAC (RAD1)

P38-2:

E4 (SDC)

P38-4:

no connection

P39: Firestat & Remote Shutdown

 

 

 

P39-1:

24

VAC Out (HTS)

 

P39-3: 24 VAC Out (RDS1)

P39-2:

24

VAC Return (HTS)

 

P39-4:

24

VAC Return (RSD1)

P40: Basic Unit Connections

 

 

 

 

P40-1:

no connections

P40-8:

E4

(Opt. CPAR)

P40-2:

no connections

P40-9:

no connection

P40-3:

no connections

P40-10:

E4

 

P40-4:

24

VAC Out (Opt. CPAR) P40-11:

no connection

P40-5:

no connections

P40-12:

24 VAC Out (MF Ovld)

P40-6:

no connections

P40-13:

24 VAC

P40-7:

no connections

 

 

 

 

P43: T6 Transformer

P43-1: 24 VAC Gnd

P43-2: 24 VAC

P51: Hot Water Reheat

 

 

P51-1:

24 VAC Out

P51-3:

H.W. Mod (0 – 2.5 VDC)

P51-2:

-5 VDC Gnd

P51-4:

24 VAC Gnd (E1)

P52: Glycool Valve (Opt. Pressure Modulating)

P52-1:

24 VAC Out

 

P52-4: 24 VAC Gnd (E1)

P52-2:

-5 VDC Gnd

 

P52-5: no connection

P52-3: Mod Valve (0 – 2.5 VDC)

 

P53:

 

 

 

P53-1:

24 VAC

 

 

P53-2:

no connection

 

 

P53-3:

no connection

 

 

P53-4:

E3

 

 

P53-5:

no connection

 

 

P54:

 

 

 

P54-1:

24 VAC

 

 

P54-2:

no connection

 

 

P54-3:

no connection

 

 

P54-4:

E3

 

 

P54-5:

no connection

 

 

109

Page 110
Image 110