Service Menu: Set Alarm Parameters: Page 5 of 6

iCOM Controls Training and Service Manual

Service Menu: Set Alarm Parameters: Page 5 of 6

 

Menu Line

Parameter

 

 

 

 

S249

Password

 

 

 

 

 

 

 

 

 

 

S250

 

DELAY

EN-DIS

TYPE

 

 

 

 

 

 

 

S251

Working Hours Exceeded

-

En

Warning

 

 

 

 

 

 

 

S252

Smoke Detected

5 Sec

En

Alarm

 

 

 

 

 

 

 

S253

Water Under Floor

5 Sec

En

Alarm

 

 

 

 

 

 

 

S254

Cond Pump-High Water

5 Sec

En

Alarm

 

 

 

 

 

 

 

S255

Loss of Flow

5 Sec

En

Alarm

 

 

 

 

 

 

 

S256

Standby Glycol Pump On

5 Sec

En

Alarm

 

 

 

 

 

 

 

S257

Standby Unit On

5 Sec

En

Alarm

 

 

 

 

 

 

 

S258

Humidifier Problem

5 Sec

En

Alarm

 

 

 

 

 

 

 

S259

No Connection w/ Unit 1

-

En

Alarm

 

 

 

 

 

 

 

S260

Unit X Disconnected

-

En

Alarm

 

 

 

 

 

 

Service Menu: Set Alarm Parameters: Page 6 of 6

 

 

 

Menu Line

Parameter

 

 

 

 

S262

Password

 

 

 

 

 

 

 

 

 

 

S263

 

DELAY

EN-DIS

TYPE

 

 

 

 

 

 

 

S264

Customer Input 1

5 Sec

En

Alarm

 

 

 

 

 

 

 

S265

Customer Input 2

5 Sec

En

Alarm

 

 

 

 

 

 

 

S266

Customer Input 3

5 Sec

En

Alarm

 

 

 

 

 

 

 

S267

Customer Input 4

5 Sec

En

Alarm

 

 

 

 

 

 

 

S268

Call Service

5 Sec

En

Message

 

 

 

 

 

 

 

S269

High Temperature

5 Sec

En

Message

 

 

 

 

 

 

 

S270

Loss of Air Blower 1

5 Sec

En

Alarm

 

 

 

 

 

 

 

S271

Reheat Lockout

5 Sec

En

Message

 

 

 

 

 

 

 

S272

Humidifier Lockout

5 Sec

En

Message

 

 

 

 

 

 

 

S273

Humid + Reheat Lockout

5 Sec

En

Message

 

 

 

 

 

 

 

S274

Compressor(s) Lockout

5 Sec

En

Message

 

 

 

 

 

 