CAT5 (Patch-cable) and

iCOM Control Training and Service Manual

Example: 2 Units, One Large Display and One Small Display

All Network parameters are viewed and programmed using the Service Menu function and by selecting the Network Setup Icon

The following example references menu lines on the Network Setup screen:

Line S802: Number units connected: xx (2)

Line S803: Teamwork: xx (No, 1, 2)

Line S804: Large Display Board IP Address: 192.168.254. xxx (001 - 049)

Line S804: Control Board IP Address: 192.168.254. xxx (050 - 099)

Line S805: Large Display Board Netmask IP: 255.255.255.000

Line S805: Control Board Netmask IP: 255.255.255.000

Line S806: Large Display Board Gateway IP: 192.168.254.255

Line S806: Control Board Gateway IP: 192.168.254.255

Line S808: U2U address Display #: xx (33 - 64)

Line S808: U2U address Control Board #: xx (1 - 32)

Line S810: U2U group #: xx (1 - 99)

CAT5 (Patch-cable) and

 

Power

(CAN)

 

 

 

Unit No. 1

Switch

Unit No. 2

45

Page 46
Image 46