Liebert TM-10098 Fuse Board Layout: All Units, iCOM Control Training and Service Manual

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 112
Image 112
Fuse Board Layout: All Units

iCOM Control Training and Service Manual

Fuse Board Layout: All Units

This section deals with the seven (7) plug connectors on the fuse board. The fuse board is supplied on all systems with iCOM and is located in the low voltage section of the unit. The tables in this section show all of the connections and reference points for signal flow through these connectors.

 

 

 

Fuse Board

P4: 24 VAC Power

 

 

P4-1:

Fuse 1

P4-3:

Fuse 3

P4-2:

Fuse 2

P4-4:

Fuse 4

P24: T1 Transformer

P24-1: 24 VAC Gnd (T1)

P24-2: 24 VAC (T1)

P41: 24 VAC Power

 

 

 

P41-1:

24

VAC Gnd (T1)

P41-3:

24

VAC Gnd (not unit ground)

P41-2:

24

VAC (T1)

P41-4:

24

VAC

P42: Intelleslot

P42-1: 24 VAC Gnd (not unit ground)

P42-2: 24 VAC

P43: T6 Transformer

P43-1: 24 VAC Gnd (not unit ground)

P43-2: 24 VAC

P44: Jumper

E1: Transformer Secondary Ground (unit ground)

111

Page 112
Image 112
Liebert TM-10098 Fuse Board Layout: All Units, iCOM Control Training and Service Manual, P4: 24 VAC Power, P44 Jumper