Humidity Control

iCOM Controls Training and Service Manual

Humidity Control

Humidification and/ or Dehumidification Required, in Percent (%)

The humidity control programs for the iCOM microprocessor is based on a calculated percent (%RH) requirement for humidification and/ or dehumidification. This percent (%RH) requirement is determined by the control type (algorithm) selected by the user.

The two (2) user selectable humidity control programs are:

Absolute Humidity, grains of moisture in the air

Relative Humidity (%RH)

Humidity Control Program Types

Absolute (predictive) Humidity Control – Factory Default Setting

Absolute (predictive) humidity control is based on the moisture content in the return air. The iCOM microprocessor control automatically adjusts the humidity control as the return air temperature deviates from the programmed temperature set point. This calculation converts the return temperature and humidity values to a moisture content value defined as either grains per cubic foot or grains per pound. This recalculated content value is compared to the content control band that is determined by the:

Programmed temperature set point

Programmed humidity set point in %RH

Programmed humidity proportional band in %RH

This automatic adjustment results in a predictive humidity control response. With absolute humidity control, the humidity control program is automatically adjusted approximately 2% RH for each degree difference between the return air temperature and the temperature set point. Note the following example: