Service Menu: Fan Settings Maintenance / Wellness Parameters: Page 2 of 8

Menu Line

S012

S013

S014

S015

S016

S017

S018

S019

Parameter

Password

Number of Starts

Run Hours

Average Working Time Starts per Day Optimum Starts per Day Worst Number of Alarms Actual Bonus

Default

-

-

-

-

1

24

-

-

Range

-

0 – 32000

0 – 32000

0 – 999 minutes

1 – 240

1 – 240

0 – 32000

0 - 12

Service Menu: Compressor 1 Settings Maintenance / Wellness Parameters: Page 3 of 8

Menu Line

S023

S024

S025

S026

S027

S028

S029

S030

S031

S032

S033

Parameter

Password

Number of Starts

Run Hours

Average Working Time Starts per Day Optimum Starts per Day Worst Number of HP Alarms Number of LP Alarms Number of OL Alarms Number of DS HT Alarms Actual Bonus

Default

-

-

-

-

12

240

-

-

-

-

-

Range

-

0 – 32000

0 – 32000

0 – 999 minutes

1 – 240

1 – 240

0 – 32000

0 – 32000

0 – 32000

0 - 32000

0 - 12