Liebert TM-10098 Menu Line, Default, Range, Service Menu: Unit Diary Log Parameter

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 69
Image 69
Service Menu: Unit Diary Log

iCOM Controls Training and Service Manual

Service Menu: Set Point Parameters S100 series: Page 2 of 2

Menu Line

S112

S113

S114

S115

S116

S117

S118

S119

S120

S121

S122

Parameter

Password

Humidity Proportional Band

Humidity Integration Time

Humidity Deadband

DT Between Room / FC Type

DT Between Room Air / FC Fluid

Minimum CW Temp

Minimum CW Temp Value

Default

-

10%

0

0

Disable

8ºF

Disable

45ºF

Range

-

1 – 20%

0 – 5 minutes

0 – 50%

Disable, Contact,

Value

0 - 36ºF

Enable / Disable

32 - 68ºF

Service Menu: Unit Diary Log

Parameter

Displays changes to the unit as performed and entered by

the service person or customer

68

Page 69
Image 69
Liebert TM-10098 service manual Menu Line, Default, Range, Service Menu: Unit Diary Log Parameter