Liebert TM-10098 Setting Parameters, Unit No, iCOM Controls Training and Service Manual

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 45
Image 45
Setting Parameters

iCOM Controls Training and Service Manual

Setting Parameters

Example: 2 Units with Small Display’s

All Network parameters are viewed and programmed using the Service Menu function and by selecting the Network Setup Icon

The following example references menu lines on the Network Setup screen:

Line S802: Number units connected: xx (2)

Line S803: Teamwork: xx (No, 1, 2)

Line S804: Control Board IP Address: 192.168.254. xxx (010, 011)

Line S805: Control Board Netmask IP the same for all units

Line S806: Control Board Gateway IP the same for all units

Line S808: U2U address Control Board #: xx (1-2)

Line S810: U2U group #: xx (1)

U2U: CAT5 (Crossover-cable)

Unit No. 1

Unit No. 2

44

Page 45
Image 45
Liebert TM-10098 Setting Parameters, Unit No, iCOM Controls Training and Service Manual, U2U: CAT5 Crossover-cable