Liebert TM-10098 iCOM Control Training and Service Manual, Menu Line, Parameter, Default, Range

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 70
Image 70
series: Page 1 of 8

iCOM Control Training and Service Manual

Service Menu: Standby Setting / Lead-lag Parameters S500 series

Menu Line

S501

S502

S503

S504

S505

S506

S507

S508

S509

S510

S511

Parameter

Password

Number of Standby Units

Rotation Frequency

Rotate at (hour)

Rotate at (minute)

Rotate by

Perform one rotation

Cascade units

Start All Standby Units by HT

Default

-

0

No

0

0

1

-

No

No

Range

-

0 – 15

No, Daily, Every M, T, W, Th, F, S, Su

0 – 23

0 – 59

1 – 8

No or Yes

No, Yes, Cool,

Temp

No or Yes

Service Menu: General Settings Maintenance / Wellness Parameters S000

series: Page 1 of 8

 

Menu Line

 

 

Parameter

 

 

Default

 

 

Range

 

 

S001

 

Password

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

S002

 

 

Maintenance Frequency Per Year

 

 

1

 

 

0 – 12 per

 

 

 

 

 

 

 

 

year

 

 

 

 

 

 

 

 

 

 

 

 

 

S003

Max Bonus

0

 

 

0 – 12

 

 

 

 

 

 

 

 

 

S004

 

 

Max Penalty

 

 

0

 

 

0 – 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S005

 

Last Maintenance

-

 

 

Date

 

 

 

 

 

 

 

 

 

S006

 

 

Service Engineer

 

 

-

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S007

 

Confirm PM

-

 

 

No or Yes

 

 

 

 

 

 

 

 

 

S008

 

 

Calculated Next Maintenance

 

 

-

 

 

Date

 

 

 

 

 

 

 

 

 

 

 

 

 

69

Page 70
Image 70
Liebert TM-10098 service manual iCOM Control Training and Service Manual, Menu Line, Parameter, Default, Range, series