Service Menu: Set Alarm Parameters: Page 2 of 6

iCOM Controls Training and Service Manual

Service Menu: Set Alarm Parameters S200 series: Page 1 of 6

 

Menu Line

 

 

Parameter

 

 

 

Default

 

 

 

 

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

S201

 

 

Password

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S202

 

 

Return Sensor Alarms

 

 

 

Enabled

 

 

Disabled or Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S203

 

 

High Return Temperature

 

 

 

80ºF

 

 

 

34 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S204

 

 

Low Return Temperature

 

 

 

 

65ºF

 

 

 

 

34 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S205

 

 

High Return Humidity

 

60%

 

 

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S206

 

 

Low Return Humidity

 

 

40%

 

 

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S207

 

 

Sensor A Alarms

 

Disabled

 

Disabled or Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S208

 

 

High Temperature Sensor A

 

 

 

 

90ºF

 

 

 

 

34 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S209

 

 

Low Temperature Sensor A

 

 

 

55ºF

 

 

 

34 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S210

 

 

High Humidity Sensor A

 

 

70%

 

 

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S211

 

 

Low Humidity Sensor A

 

30%

 

 

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Menu: Set Alarm Parameters: Page 2 of 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Menu Line

 

 

 

Parameter

 

 

Default

 

 

Range

 

 

S212

Password

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

S213

 

Customer Input 1

 

 

Water alarm

 

See note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S214

Customer Input 1 Active When

 

 

Closed

 

 

Open or Closed

 

 

 

 

 

 

 

 

 

S215

 

Customer Input 2

 

 

Water alarm

 

See note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S216

Customer Input 2 Active When

 

 

Closed

 

 

Open or Closed

 

 

 

 

 

 

 

 

 

S217

 

Customer Input 3

 

 

Water alarm

 

See note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S218

Customer Input 3 Active When

 

 

Closed

 

 

Open or Closed

 

 

 

 

 

 

 

 

 

S219

 

Customer Input 4

 

 

Water alarm

 

See note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S220

Customer Input 4 Active When

 

 

Closed

 

 

Open or Closed

 

 

 

 

 

 

 

 

 

 

S221

 

Warning Activates Alarm Relay

 

 

Yes

 

 

Yes or No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S222

Reset Disabled Alarms

 

 

No

 

 

Yes or No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Customer Inputs 1, 2, 3 and 4 messages may be selected from Smoke Detected, Water Alarm, Condensate Pump Alarm, Flow Alarm, Standby Pump, Standby Unit.