iCOM Control Training and Service Manual

Advanced Menu: Factory Settings Parameters: Page 6 of 6

Menu Code

Parameter

Default

Range

 

 

 

 

A145

Password

-

-

 

 

 

 

A146

Humidifier Model

No

No, external, IFS, IFL

 

 

 

 

A147

Humidity in Last

15hr

1 - 120 hours

xx Hours

 

 

 

A148

Prefill Time

IFS 30

1 - 120 seconds

IFL 60

 

 

 

A149

Fill Time

IFS 30

1 - 120 seconds

IFL 50

 

 

 

A150

Humidifier On

IFS 8

1 - 60 minutes

Time

IFL 10

 

 

A151

Dehum with

2

1, 2, both

Compressor

 

 

 

A152

Analog Output 1

Not used

* See note 3

 

 

 

 

A153

Analog Output 2

Not used

*See note 3

 

 

 

 

A154

Analog Output 3

Not used

* See note 3

 

 

 

 

A155

Analog Output 4

Not used

* See note 3

 

 

 

 

Note 1: LP threshold Phase 1 (A117):

If condenser ctrl (A132) = fan speed then setting is 50 psiA ; otherwise 75 psiA. If the condenser control setting changes, the setting for A117 will be updated automatically. If any of the sources (Refrigerant, Freecooling, Hotwater) changes, the setting for A118 will be updated automatically.

Note 2: LP threshold Phase 1 (A118):

R22 (A102) + NO FC (A137) + NO Hotwater (S408) = 63 psiA

R22 (A102) + YES FC (A137) + NO Hotwater (S408) = 68 psiA R22 (A102) + NO FC (A137) + YES Hotwater (S408) = 75 psiA R22 (A102) + YES FC (A137) + YES Hotwater (S408) = 75 psiA R407c (A102) + NO FC (A137) + NO Hotwater (S408) = 70 psiA R407c (A102) + YES FC (A137) + NO Hotwater (S408) = 75 psiA R407c (A102) + NO FC (A137) + YES Hotwater (S408) = 83 psiA R407c (A102) + YES FC (A137) + YES Hotwater (S408) = 83 psiA

Note 3: The following components may be controlled with the Analog Outputs and

labeled as: Hot Water Reheat, 3P Valve, Fan Speed, Cooling, Cooling 1, Cooling 2, Heating and Not Used.