Isolation

iCOM Control Training and Service Manual

The temperature sensor senses a rise in temperature. The rise is transmitted to the Central Processing Unit (CPU). The CPU looks into its memory for information and instructions on what to do with the rise in temperature. The CPU then makes the decision to call for cooling.

Isolation

We use the opto-isolator and the triac to isolate areas of control and voltage. There are three areas of control and two voltage levels. Digital control comes from the microprocessor at 5 VDC and the other voltage level is 24 VAC. One voltage is used to turn on the triac and the other is used to operate the load device.

DIGITAL

Processor

5 VDC Signal

OPTO

5VDC Ground

CONTROL

Transformer Power 24 VAC

POWER

TRIAC

Load

Device

Transformer

Power 24 VAC

ISOLATIONISOLATION

Areas of Control