Liebert TM-10098 service manual iCOM Controls Training and Service Manual, P32: Compressor Devices

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 109
Image 109
P22: Glycool Valve (Std. Pressure Actuator)

iCOM Controls Training and Service Manual

P22: Glycool Valve (Std. Pressure Actuator)

 

 

P22-1:

24

VAC Out (Close Q18)

P22-4:

DCV Signal

P22-2:

DCV Signal

P22-5: E2 (24 VAC Gnd)

P22-3:

24

VAC Out (Open Q17)

P22-6:

+5 VDC

P32: Compressor Devices

 

 

 

P32-1:

24

VAC Out (LLSV1)

P32-8:

 

24 VAC

P32-2:

E1 (LLSV1)

P32-9:

 

24 VAC (HP1 Alarm)

P32-3:

24

VAC Out (LLSV2)

P32-10: 24 VAC Out (C1)

P32-4:

24

VAC Out (OL/ KL1/ HP1)

P32-11:

E1 (C1)

P32-5:

24

VAC Out (OL/ KL2/ HP2)

P32-12: 24 VAC Out (C2)

P32-6:

24

VAC (HP1)

P32-13:

E2 (C2)

P32-7:

24

VAC (HP2)

 

 

 

P33: Compressor Devices

 

 

 

P33-1:

24

VAC Out (CUV1/ DSV1)

P33-7:

24 VAC (OL/ KL2 Alarm)

P33-2:

E1 (CUV1/ DSV1)

P33-8:

24 VAC

P33-3:

E2 (LLSV2)

P33-9:

24 VAC (HP2 Alarm)

P33-4:

24

VAC Out (CUV2/ DSV2)

P33-10:

 

P33-5:

E2 (CUV2/ DSV2)

P33-11:

 

P33-6:

24

VAC (OL/ KL1 Alarm)

P33-12:

 

P34: Reheat Devices

 

 

 

P34-1:

24

VAC Out (RS1/ RS2/ RS3) P34-7:

 

no connection

P34-2:

E3 (RS1/ RS2/ RS3)

P34-8: 24 VAC Out (RH3)

P34-3:

E3 (GCD/ BR)

P34-9:

 

no connection

P34-4:

24 VAC Out (RH1/ HGRS)

P34-10: E3 (RH1/ HGRS/ RH2/ RH3)

P34-5:

no connection

P34-11:

no connection

P34-6:

24

VAC Out (RH2)

P34-12:

24 VAC Out (GCD/ BR)

P35: Infrared Humidifier Devices

 

 

 

P35-1:

24

VAC Out (H)

P35-4:

E4 (HMV)

P35-2:

E3 (H)

P35-5:

E3 (HS3)

P35-3:

24

VAC Out (HMV)

P35-6:

24 VAC Out (HS3)

P36: Basic Unit Connections

 

 

 

P36-1:

24

VAC Out (Filter Clog)

P36-9:

no connection

P36-2:

24

VAC (Filter Clog Alarm)

P36-10:

E2

P36-3:

24

VAC Out (MF)

P36-11:

No connection

P36-4:

24

VAC Out (AS Switch)

P36-12:

No connection

P36-5:

24

VAC (AS Alarm)

P36-13:

K3 (Common: TB75)

P36-6:

24

VAC (MF Ovld Alarm)

P36-14: K3 (N.O.: TB76/ R3)

P36-7:

24

VAC

P36-15:

K3 (N.C.)

P36-8:

E4 (MF)

 

 

 

108

Page 109
Image 109
Liebert TM-10098 iCOM Controls Training and Service Manual, P22 Glycool Valve Std. Pressure Actuator, P34: Reheat Devices