Advanced Menu Parameters

iCOM Controls Training and Service Manual

Advanced Menu Parameters

The Advanced menu displays allows the service technician to set the unit configuration code and to customize the various unit settings for site-specific operation. The factory default password to access the advanced menu items for programming is “221”. The Advance Menu selections include the following choices in the order shown:

Factory Settings

Access Levels

Advanced Menu: Factory Settings Parameters A001 series: Page 1 of 6

Menu Code

Parameter

Range

A001

Password

-

 

 

 

A002

Unit field code (R)

(01 – 06)

A003

Set code (W)

(01 – 06)

 

 

 

A004

Unit field code (R)

(07 – 12)

A005

Set code (W)

(07 – 12)

 

 

 

A006

Unit field code (R)

(13 – 18)

A007

Set code (W)

(13 – 18)

 

 

 

A008

Unit Code Control

No

Load+Execute

 

 

Save+Execute

A009

 

No

Unit Code Status

Load+Execute

 

 

Save+Execute

A010

Exception List Control

No, Load

A011

 

No

Exception List Status

Load+Execute

 

 

Save+Execute