iCOM Control Training and Service Manual

Advanced Menu: Factory Settings Parameters A100 series: Page 2 of 6

Menu Code

Function

Default

Range

 

 

 

 

A101

Password

-

-

 

 

 

 

A102

Refrigerant Type

R22

R22, R407C

 

 

 

 

A103

Main Fan Overload

Shut down

Shut down, Disable

 

 

 

 

A104

Loss of Airflow

Shut down

Shut down, Disable

 

 

 

 

A105

Number of Compressors

2

0, 1, 2

 

 

 

 

A106

Compressor Delay Time

0

0 - 120 Sec

 

 

 

 

A107

Compressor Minimum

3 Min

0 - 5 Min

On Time

 

 

 

A108

Compressor Minimum

3 Min

0 - 5 Min

Off Time

 

 

 

A109

Pump Down

Yes

No, Yes

 

 

 

 

A110

Capacity Control Type

Unloader

No, Unloader, HGBP,

Digital, Digital + TH

 

 

 

 

 

 

 

Advanced Menu: Factory Settings Parameters A100 series: Page 3 of 6

Menu Code

Parameter

Default

Range

 

 

 

 

A112

Password

-

-

 

 

 

 

A113

Digi Scroll Cycle

15

No, 10 - 30 Sec

 

 

 

 

A114

High Temperature Digi

268°F

33 - 392°F

Scroll

 

 

 

A115

Digi Scroll Switchback

250°F

33 - 392°F

 

 

 

 

A116

Low Pressure Device

Analog

Analog, Switch

Type

 

 

 

A117

Low Pressure Threshold

* See Note 1

0.0 - 145 psiA

Phase 1

 

 

 

A118

Low Pressure Threshold

* See Note 2

0.0 - 145 psiA

Phase 2

 

 

 