Service Menu Parameters

iCOM Control Training and Service Manual

Service Menu Parameters

The Service menu display allows the user to customize the various unit settings for site specific operation. The factory default password to access the service menu items for programming is “501”. The Service Menu selections include the following choices in the order shown:

Set Point Parameters

Unit Diary

Standby Settings Parameters

Maintenance / Wellness Setting Parameters

Diagnostic / Service Mode Parameters

Set Alarm Parameters

Sensor Calibration / Setup Parameters

System / Network Setup Parameters

Operations Setup Parameters

Service Contacts Parameters

Service Menu: Set Point Parameters S100 series: Page 1 of 2

Menu Line

Parameter

Default

Range

S101

Password

-

-

 

 

 

 

S102

Temperature Setpoint

73ºF

41 - 104ºF

 

 

 

 

S103

Humidity Setpoint

50%

1 – 80%

 

 

 

 

S104

Humidity Control Type

Yes

Yes or No

 

 

 

 

S105

Supply Limit

Disabled

Disabled or Enabled

 

 

 

 

S106

Supply Limit Temp Value

41ºF

41 - 77ºF

 

 

 

 

S107

Autoset Enable

Yes

Yes or No

 

 

 

 

S108

Temperature Proportional Band

7ºF

2 - 54ºF

 

 

 

 

S109

Temperature Integration Time

0

0 – 5 minutes

 

 

 

 

S110

Temperature Deadband

0

0 - 36ºF

 

 

 

 

S111

Short Cycle Control

Yes

Yes or No

 

 

 

 