iCOM Controls Training and Service Manual

Advanced Menu: Factory Settings Parameters: Page 4 of 6

Menu Code

Parameter

Default

Range

 

 

 

 

A123

Password

-

-

 

 

 

 

A124

LP1 Sensor

10%

0 - 100%

 

 

 

 

A125

LP1 Signal

150 psiA

-87.0 to +725 psiA

 

 

 

 

A126

Actual LP1 Signal

-

0 - 100%

 

 

 

 

A127

LP2 Sensor

10%

0 - 100%

 

 

 

 

A128

LP2 Signal

150 psiA

-87.0 to +725 psiA

 

 

 

 

A129

Actual LP2 Signal

-

0 - 100%

 

 

 

 

A130

Pumpdown Cutout

35 psiA

0.0 - 145 psiA

 

 

 

 

A131

Pumpdown Recycle

80 psiA

0.0 - 145 psiA

 

 

 

 

A132

Heat Rejection Control

Fan Speed

Fan Speed /

Type

Lee-Temp / Glycol

 

 

 

 

 

 

Advanced Menu: Factory Settings Parameters A100 series: Page 5 of 6

Menu Code

Parameter

Default

Range

A134

Password

-

-

 

 

 

 

A135

 

 

 

 

 

 

 

A136

CW flush Duration

0

No, 1 - 3 min

 

 

 

 

A137

Freecooling

No

No, Yes

 

 

 

 

A138

 

 

 

 

 

 

 

A139

Freecooling Flush Duration

0

No, 1 - 3 min

 

 

 

 

A140

Freecooling Flush Starts R5

Yes

No, Yes

 

 

 

 

A141

CO + FC simultaneously

Yes

No, Yes

 

 

 

 

A142

 

 

 

 

 

 

 

A143

Hot water flush duration

0

No, 1 - 3 min

 

 

 

 

86

Page 87
Image 87
Liebert TM-10098 service manual iCOM Controls Training and Service Manual, Menu Code, Parameter, Default, Range