STAGE TEMPERATURE

iCOM Controls Training and Service Manual

The example below is based on a temperature set point of 70°F with a control band length of 4°F, which is ½ of the programmed temperature proportional band value.

STAGE TEMPERATURE

Cool 1 ON

Set point plus 1°F

 

 

Cool 2 ON

Set point plus 2°F

 

 

Cool 3 ON

Set point plus 3°F

 

 

Cool 4 ON

Set point plus 4°F

 

 

Cool 4 OFF

Set point plus 3°F

 

 

Cool 3 OFF

Set point plus 2°F

 

 

Cool 2 OFF

Set point plus 1°F

 

 

Cool 1 OFF

Set point

 

 

4 Stage Compressorized Cooling – With Dead Band

Temp Set Point + (1/2 Dead Band + 1/2 Proportional Band)

Temp Set Point: 70°F

 

 

 

 

Proportional Band: 8°F

 

Cool 2 On

Cool 4 On

Dead Band: 2°F

 

 

 

 

 

 

 

 

 

Cool 1 On

 

Cool 3 On

70

71

72

73

74

75

DB

 

 

 

 

 

 

 

Cool 2 Off

 

Cool 4 Off

 

Cool 1 Off

Cool 3 Off

 

 

Increasing Temperature

 

 

 

Note: in the above example that the control band begins at the 70°F temperature set point and has a length of 5°F, which is ½ of the programmed temperature dead band value plus ½ of the programmed temperature proportional band value.