iCOM Controls Training and Service Manual

072

COMP 2

Compressor 2 stopped

Alarm

no

yes

yes

 

OVERLOAD

because of overload

 

 

 

(broken co

 

 

 

 

 

 

will remain

 

 

 

 

 

 

off)

079

UNIT

this message appears

Message

 

-

-

 

DISABLED

after a critical alarm

 

 

 

 

 

 

(airflow, main fan

 

 

 

 

 

 

overload) and indicates

 

 

 

 

 

 

that the unit is operating

 

 

 

 

 

 

w/o humidifier or

 

 

 

 

 

 

electrical heaters.

 

 

 

 

 

 

 

 

 

 

 

080

UNIT SHUT

this message appears

Message

 

-

-

 

DOWN

after a critical alarm

 

 

 

 

 

 

(airflow, main fan

 

 

 

 

 

 

overload) and indicates

 

 

 

 

 

 

that the unit is shut down

 

 

 

 

 

 

due to the alarm.

 

 

 

 

085

UNIT

a unit came back into the

Message

-

-

-

 

SYNCHRONIS

network.

 

 

 

 

 

ATION

 

 

 

 

 

086

HUMIDIFIER

humidifier

Alarm

no

yes

 

 

PROBLEM

overtemperature or high

 

 

 

 

 

 

water level

 

 

 

 

088

DEHUM HRS

actual working hours of

Warning

no

no

 

 

EXCEEDED

dehumidification are

 

 

 

 

 

 

higher than the threshold

 

 

 

 

 

 

set.

 

 

 

 

089

FC HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

freecooling are higher

 

 

 

 

 

 

than the threshold set.

 

 

 

 

091

COMP 1

Pump down of circuit 1

Alarm

no

yes

yes

 

PUMPDOWN

was not completed

 

 

 

(broken co

 

FAIL

(pressure value not

 

 

 

will remain

 

 

reached).

 

 

 

off)

096

COMP 2

Pump down of circuit 2

Alarm

no

yes

yes

 

PUMPDOWN

was not completed

 

 

 

(broken co

 

FAIL

(pressure value not

 

 

 

will remain

 

 

reached).

 

 

 

off)

097

DIG SCROLL1

Digital Scroll compressor

Alarm

no

yes

yes

 

HIGH TEMP

#1 shut off because of

 

 

 

(broken co

 

 

high temperature (sensor

 

 

 

will remain

 

 

is inside the

 

 

 

off)

 

 

compressor).

 

 

 

 