Liebert TM-10098 iCOM Controls Training and Service Manual, Menu Line, Parameter, Default, Range

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 81
Image 81
Function

iCOM Controls Training and Service Manual

Service Menu: Sensor Calibration/ Setup Parameters: Page 3 of 3

Menu Line

S623

S624

S625

S626

S627

S628

S629

S630

S631

S632

S633

Parameter

Password

Glycol sensor PTC or NTC Glycol sensor Calibrated glycol sensor Supply sensor PTC or NTC Supply sensor Calibrated supply sensor Temperature sensor C Calibrated temperature sensor C Humidity sensor C Calibrated humidity sensor C

Default

NTC

-

-

NTC

-

-

-

-

-

-

Range

-

NTC or PTC

±17ºF

4 – 113ºF

NTC or PTC

±17ºF

32 - 122ºF

±17ºF

32 - 122ºF

±9.9%

20 – 80%

Service Menu: System / Network Setup Parameters Series S800: Page 1 of 2, System View

 

Menu Line

 

 

Function

 

 

Default

 

 

Range

 

 

 

 

 

 

 

 

 

 

S801

 

Password

-

 

-

 

 

 

 

 

 

 

 

 

 

S802

 

 

Number of connected units

 

 

-

 

 

1 – 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S803

 

Teamwork mode

 

No

 

No, 1, 2

 

 

 

 

 

 

 

 

 

 

 

 

S804

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S805

 

 

U2U group

 

 

-

 

 

1 - 99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S806

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S807

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S808

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S809

 

Configuration Safe Status

 

No

 

No, Save, Load

 

 

 

 

 

 

 

 

 

S810

 

 

Network Safe Status

 

 

-

 

 

No, Save, Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S811

 

SW version:

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

Page 81
Image 81
Liebert TM-10098 service manual iCOM Controls Training and Service Manual, Menu Line, Parameter, Default, Range, Function