Unit Code Description

iCOM Control Training and Service Manual

Unit Code Description

The iCOM controller uses a system parameters auto configuration methodology. The unit will have a code on a serial tag displayed on the front of the electric panel. This code when entered during the factory QA process will define unit configuration and auto set various parameters for functionality. The sheets in the back of this manual will allow the service technician to understand and be able to enter this unit code manually if necessary through the control panel and

the FACTORY SETTINGS parameter. The parameter codes are listed in Chapter as A001 to A011. The UNIT CODE ID numbers must be entered in groups of six at a time. When all ID numbers of the UNIT CODE are entered user must select

A008 to “Send and Execute Unit Code” then verify parameter code A011 for a “VALID” status. If UNIT CODE is missing or lost the unit will not start until the correct code is entered and saved.

The UNIT CODE sheets will show a VALUE field on the left of the first page and followed by 18 columns of unit configuration definitions.

THIS UNIT CODE IS NOT TO BE CHANGED UNLESS INSTRUCTED BY A

FACTORY SERVICE TECHNICIAN.

145

Page 146
Image 146
Liebert TM-10098 service manual Unit Code Description, iCOM Control Training and Service Manual, Factory Service Technician