Commissioning

Detailed description of RS commands

SBY Switches the speed set point to the stand-by value

Syntax #adrSBY<CR>[<LF>]

Result #adr,ok

See also: NSP, RPM

SEL

Syntax

Result

Resets the stand-by speed to its last stored value, and allows it to be modified if an “RPM” command is sent.

This configuration is automatically stored in user memory.

Returns the state of the parameters defined by OPT

#adrSEL<CR>[<LF>]

#adr,a,u a: Reserved

u: Returns the choice of temperature unit::

u = 0: degrees Centigrade

u = 1: degrees Fahrenheit

January 2001

 

SEP

 

 

Defines the character which separates the parameters

 

 

 

 

in a reply

 

 

 

 

 

 

 

Syntax

 

 

#adrSEPnnn<CR>[<LF>]

 

 

 

 

3-digit decimal value of the ASCII code of the desired char-

 

 

 

 

acter (with leading zeros if necessary).

 

 

 

 

condition: 000

nnn 255

 

Result

 

 

#adr,ok or #adr,ErrX

if error

 

 

 

 

Allows the user to select the character which separates

 

 

 

 

the parameters returned by the DLR, STA and LEV

 

 

 

 

commands. Default value: comma “,” ASCII code = 044

 

 

 

 

If ok, the selected value is automatically stored in user memory.

 

 

Alcatel Vacuum Technology France - ACT 250 addendum

21

Page 22
Image 22
Alcatel Carrier Internetworking Solutions ACT 250 user manual Sel, Defines the character which separates the parameters