Sprinkler Option Temperature Controller Settings
NOTE: Refer to Controller’s User’s Manual for further information on controller options.
Message | Message | Settings | |
Display | Description | ||
| |||
|
|
| |
SECr | SECURITY CODE | FULL SECURITY - SET TO 110 (DISPLAYED AS 1) "VIEW ONLY" | |
NO SECURITY - SET TO 111 (DISPLAYED AS 4) | |||
|
| "ALL FEATURES UNLOCKED" | |
|
|
| |
InP | INPUT DEVICE | P 385 = RTD INPUT | |
|
|
| |
º F OR º C | SELECT TYPE REQUIRED (FAHRENHEIT OR CELSIUS) | ||
|
|
| |
dPt | DECIMAL POINT | 0, NO DECIMAL POINT | |
|
|
| |
InPt | INPUT FAULT TIMER | 0.2 | |
|
|
| |
SPL | SET POINT LOW | 500 (SETTING CANNOT BE LOWER) | |
|
|
| |
SPH | SET POINT HIGH | 700 (SETTING CANNOT BE HIGHER) | |
|
|
| |
SPSt | SET POINT STATE | rE (REVERSE ACTION) | |
|
|
| |
SPLP | SET POINT LAMP | 0 oFF (LAMP OFF WHEN OUTPUT IS ON) | |
|
|
| |
AL | HIGH ALARM ONLY | Hi | |
|
|
| |
ALt | ALARM TYPE | Abs (ABSOLUTE ALARM) | |
|
|
| |
ALrE | ALARM RESET | OnOF (AUTOMATIC RESET) | |
|
|
| |
ALPi | ALARM POWER | OFF (ALARM INHIBIT IS OFF) | |
INTERRUPT | |||
|
| ||
|
|
| |
ALiH | ALARM INHIBIT | OFF (ALARM INHIBIT IS OFF) | |
|
|
| |
ALSt | ALARM OUTPUT | CLOS | |
STATE | (CLOSES CONTACTS AT ALARM SET POINT) | ||
| |||
|
|
| |
ALLP | ALARM LAMP | 0 ON (ALARM LAMP IS ON WHEN ALARM CONTACT IS CLOSED) | |
|
|
| |
ALHi | ALARM HI | 575º F OR 301.6º C (NOTE: ADJUST SAME AS SP) | |
|
|
| |
Cy | CYCLE RATE | OnOF | |
|
|
| |
SP_d | SET POINT | ||
DIFFERENTIAL | |||
|
| ||
|
|
| |
rt | RAMP TIME | OFF | |
|
|
| |
InPC | INPUT CORRECTION | 0 | |
|
|
| |
FiLt | DIGITAL FILTER | 2 | |
|
|
| |
SP | TEMPERATURE | 575º F OR 301.6º C | |
SET POINT | |||
|
| ||
|
|
|
Note: When message display (Cy) set to OnOF.
SPOL (SET POINT OUTPUT LOW LIMIT) not in use.
SPOH (SET POINT OUTPUT HIGH LIMIT) not in use.
Are not displayed.
75