American Power Conversion AP7601, AP7608, AP7602 How to Download Firmware Updates, Xmodem

Models: AP7602 AP7608 AP7601

1 24
Download 24 pages 17.11 Kb
Page 20
Image 20
How to Download Firmware Updates

How to Download Firmware Updates

You can use a local computer that connects to the Rack PDU through the serial port on the front of the unit.

1.Select a serial port at the local computer, and disable any service that uses that port.

2.Use the configuration cable to connect the selected port to the RJ-12 serial port on the front panel of the Rack PDU.

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.

4.Press ENTER twice to display the User Name prompt.

5.Enter your User Name and Password (both apc, for administrators only) and press the ENTER key.

6.From the Control Console menu, select System, then Tools, then

XMODEM.

7.The system will prompt you with Perform transfer with XMODEM -CRC? Type Yes and press ENTER.

8.The system will then prompt you to choose a transfer rate and to change your terminal settings to match the transfer rate. Press ENTER to set the Rack PDU to accept the download.

9.In the terminal program, send the file using the XMODEM protocol. Upon completion of the transfer, the console will prompt you to restore the baud rate to normal.

Do not interrupt the download.

Caution

The Rack PDU will reboot when the download is complete.

Upgrading the firmware will not interfere with the operation of the outlets.

Note

16

Three-Phase Rack PDU — Installation and Operation Manual

Page 20
Image 20
American Power Conversion AP7601, AP7608, AP7602 operation manual How to Download Firmware Updates, Xmodem