Fluid Level

 

Tube

Optimum

 

Fluid Level

Fill Range

Indicator

 

Battery Fill Cap

 

Float Device

 

Figure 3. Battery Fill Cap Elements

Check Battery Charge Level - After filling battery cells (if necessary), check the battery specific gravity using a hydrometer. The battery specific gravity should be between 1230 and 1250. If battery specific gravity is below 1230, charge the battery using a battery charger until the battery specific gravity is within the acceptable range.

!Warning: Each battery weighs 28 kg. Two-person lift required. Failure to comply may result in personal injury.

Repackage Battery - Place the battery in the shipping container by grasping the handles located at each end of the battery. Lift the battery straight upwards and place it in the shipping container. Install packaging materials. Seal the shipping container, and ship the battery to the customer location.

Section 2. Unpacking/Inspection (at customer location)

Main Housing Chassis and Inverter

Note: The Inverter Assembly is shipped with two (one male and one female) IEC connectors for use in installing home wiring to/from the Inverter.

Inspect the shipping containers for signs of obvious damage. If damage to either shipping container is extensive, notify the carrier and return the unit to the factory. If there are no apparent signs of damage to the shipping container, carefully open the container, and remove the packing materials (do not discard).

!Warning: The Main Housing weighs 18 kg. Two-person lift required. Failure to comply may result in personal injury.

To remove the Main Housing Chassis or Inverter from the shipping container, grasp the handles located on each side of the Housing or Inverter (Figure 1), and remove the item from the shipping container. Inspect each for: dents, scratches, broken or missing wheels (housing only), warpage of the top cover, or other signs of damage. If either unit is damaged, please notify the factory and obtain a Return Material Authorization number and return the unit as/if instructed. If there are no obvious signs of damage, proceed with Battery Inspection.

Page 3

Page 6
Image 6