Specifications
| Table 3. APC Power Inverter Technical Specifications | |
| Item | Specification |
|
|
|
Input | Nominal Voltage | 230 V |
Characteristics |
|
|
| Rated Voltage | 230 V |
| Frequency | |
| Nominal Rated Current | 3.47 A |
| Input Circuit Breaker Rating | 10 A |
| Input Voltage Window for Utility Operation | 100 - 265 VAC |
|
|
|
Output | Voltage (on Mains) | 100 - 265 VAC |
Characteristics |
|
|
| Voltage (on battery) | 210 - 240 VAC |
| Rated VA | 800 VA |
| Rated Watts | 500 W |
| Nominal Rated Current | 3.47 A |
| Overload Indicated ON BATTERY | >100% |
| Shutdown due to OVERLOAD | > 100% after 60 seconds (see Table 1 and following note) |
| Frequency (ON BATTERY) | 50 Hz +/- 1% |
|
|
|
Surge | Protects the load from surges and spikes.. | |
Protection |
|
|
Environmental | Ambient Operating Temperature | |
| Humidity | 95 % Relative humidity, |
| Altitude | 3000 m |
|
|
|
Physical | Input Line | IEC socket |
| Outlet Receptacles | IEC socket |
| Dimensions - Unit (h) x (w) x (d) | Main Housing Chassis: 51.2 x 47.5 x 43.0 cm |
|
| Inverter Assembly: 13.0 x 50.6 x 29.3 cm |
|
| Battery: 27.94 x 17.78 x 41.27 cm |
| Weight | Main Housing Chassis: 18 kg |
|
| Inverter Assembly: 13.5 kg |
|
| Battery: 28 kg |
| Shipping Weight | Main Housing Chassis: 20.5 kg |
|
| Inverter Assembly: 14.5 kg |
|
| Battery: XX kg (each) |
|
|
|
Batteries | Type | Two 12 V, 70 |
| Typical Runtime | Approximately 120 minutes |
| Typical Load Set Up | |
|
| |
| Runtime at 500 W | Approximately 120 minutes |
| Typical Recharge Time (for a 90% Charge | |
| Following a 50% Discharge) |
|
| AC Input Voltage Range for Charging | 100 - 265 V |
|
|
|
Page 14