Specifications

SU041,

SU042-1, SU042-2, and SU042-4

Item

 

Specification

 

 

 

 

Power

 

 

 

 

 

 

Nominal input voltage

120 VAC

 

 

 

 

Input voltage range

0 165 VAC

 

 

 

 

Frequency range

47 63 Hz

 

 

 

Normal sensitivity transfer times

8 ms maximum at 60 Hz

10 ms maximum at 50 Hz

 

 

 

Reduced sensitivity transfer

16 ms maximum at 60 Hz

times

20 ms maximum at 50 Hz

 

 

Maximum current draw

12 A (SU041 model)

24 A (SU042 models)

 

 

 

 

 

Physical

 

 

 

 

 

 

 

Size:

1.75 ×

17.0 ×

7.5 in

4.45 ×

43.2 ×

19 cm

 

 

 

 

Net weight

10 lb (4.5 kg)

 

 

 

 

Shipping weight

15 lb (6.8 kg)

 

 

 

 

 

Environmental

 

 

 

 

 

 

 

Elevation (above MSL):

 

 

 

• Operating

0 to 10,000 ft (0 to 3000 m)

• Storage

0 to 50,000 ft (0 to 1500 m)

 

 

 

 

Temperature:

 

 

 

• Operating

32° to 122° F (0 to 50° C)

• Storage

5° to 122° F (– 15° to 50° C)

 

 

 

 

Relative Humidity

 

 

 

(Operating and Storage)

0 to 95%, non-condensing

 

 

 

 

Approvals/Standards

UL, CSA, FCC Class A

20