Configuration

 

 

 

 

b. Restart the computer on which PowerChute plus is

 

 

installed.

 

 

c. Start PowerChute plus. Communication is to UPS-A.

 

 

d. Configure UPS-A according to your requirements.

 

 

e. Set the UPSID to UPS_A.

When one UPS

When one of the two UPSs becomes unavailable to supply AC

becomes

power, PowerChute plus sends the message “Self test failed:

unavailable

invalid test.” Any of the following conditions will cause the

 

message to occur:

 

A UPS self-test fails.

 

Communication with the alternate UPS is lost.

 

The voltage of the alternate UPS is out of range.

UPS-A fails, and the Redundant Switch transfers the power input and PowerChute plus communication to UPS-B.

To regain high availability for your system, correct the problem as soon as possible. See “Troubleshooting” on pa ge18.

Note

When any self-test of the primary UPS occurs, the Redundant Switch switches power and communication to the other UPS, causes a self- test of that UPS, and then switches back. This is normal behavior.