Operation

 

Emergency

You can use a remotely operated Emergency Power Off (EPO)

Power Off

switch to turn off the UPS and disconnect power to the

 

equipment load. When you turn off the UPS through the

 

Emergency Power Off system, it will turn off immediately

 

without switching to battery operation.

Electrical Hazard

Use only a licensed electrician to perform the following procedure to connect the Redundant Switch and its attached UPSs to your Emergency Power Off system.

1.Use the EPO connector.

2.Use a normally-open contact to connect the +24 terminal to the IN terminal.

3.Wire the external blue four-pin female connector to the emergency power off system.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits.

The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay

Caution

properly isolated from the utility. To avoid

 

 

damage to the Redundant Switch, do not connect

 

the EPO interface to any circuit other than a

 

closure type circuit.

16

APC Redundant Switch: Installation and Operation Manual

Page 20
Image 20
American Power Conversion Redundant Switch operation manual You can use a remotely operated Emergency Power Off EPO