TERMINATION ELBOW
NOTE: VENT PIPE MUST BE SUPPORTED EVERY 4 ft. (1.2m). TO PREVENT VIBRATION, USE ISOLATION PADS WHEN ATTACHING STRAPS TO FLOOR JOISTS, WALLS OR CEILINGS.
45°
ELBOW
STRAP
90°
RODENT SCREEN (INSTALL INTO ELBOW)
GROUND LEVEL OR
MAXIMUM SNOW
LINE*
Example for calculating equivalent feet. Section “A” . . . . 0.5 ft. . . (0.15m)
90° elbow . . . . . 7.0 ft. . . (2.13m) Section B . . . . . 1.0 ft. . . (0.31m) 45° elbow . . . . . 4.0 ft. . . (1.21m) Section C . . . . . 1.5 ft. . . (0.46m) 45° elbow . . . . . 4.0 ft. . . (1.21m) Section D . . . . . 15.0 ft. . (4.57m) Total Equivalent 33.0 ft. . (10.04m)
Based on this example use the (fully open) rodent screen for vent length greater than 20 equivalent ft. (6.1 equivalent metres).
Vent piping must slope up from heater to termination a minimum of 1/8 in. (0.3cm) rise per 4 ft. (1.2m) of vent piping
ELBOW
6in.
(15cm)
MIN.
FIGURE 21
If using 2 inch vent pipe:
Install the rubber coupling and gear clamps (supplied) at the end of the section of vent pipe installed on the heater. Continue building the vent system, or connect the existing vent system to the coupling. The total vent system must not exceed the lengths discussed above, where each (short radius) elbow is equal to 7 equivalent feet (2.1m) of straight pipe. The elbow and rodent screen supplied in the vent kit must be used as the vent termination.
If using 3 inch vent pipe:
Install the rubber reducing coupling (2 in. to 3 in.) and gear clamps (supplied) at the end of the section of vent pipe installed on the heater. Continue building the vent system, or connect the existing vent system to the coupling. The total system must not exceed the equivalent pipe lengths discussed above where each (long radius) elbow is equal to 5 ft. (1.5m) of 3 in. diameter straight vent pipe. The elbow and rodent screen supplied in the vent kit must be used as the vent termination.
NOTE: This unit can be vented with PVC pipe materials (DWV
This water heater is supplied with a 45 degree termination elbow that is a special fitting that must be used with the appliance.
PVC Materials should use ASTM
If the water heater is being installed as a replacement for an existing power vented heater in
NOTE: (A.) For water heaters in locations with high ambient temperatures (above 100°F (38°C)) it is recommended that CPVC or ABS pipe and fittings be used. (B.) A 22.5 degree elbow (2 in. vent pipe) or a 45 degree elbow (3 in. vent pipe) with an installed screen VENT TERMINAL must be used in all cases.
4.There will be some installations where condensate will be formed in the horizontal runs of the vent system. This condensate will run into the condensate trap. The water heater is shipped with a condensate tube that attaches to the condensate trap. No other tee or fitting is required.
24 | www.americanwaterheater.com |