Fault Code Troubleshooting Guide

ohms indicates good; high resistance indicates the switch is defective and should be replaced.

Heat Pump High Temperature Fault (Compressor discharge temperature is too high):

The refrigerant system may be blocked-

Check the heat pump piping and evaporator; if the tubing or evaporator is covered with frost in one spot, this indicates there is a restriction in the system at that point. Call technical services for assistance.

Check the condition of the compressor-

See the “Compressor Check Flowchart” (p.28). Water temperature is too high-

The control board is not controling the tank temperature properly

Check the upper and lower tank thermisitors; make sure they are in contact with the tank wall.

Check the tank temperature sensors, see “Temperature Sensors” (p.32).

Main Control Board Crystal Fault (Main board failure):

Faulty control board-

Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Main Control Board RAM Fault (Main board failure):

Faulty control board-

Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Main Control Board ROM Fault (Main board failure):

Faulty control board-

Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Main Control Board EEPROM Fault (Main board failure):

Faulty control board-

Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Main Control Board State Fault (Main board failure):

Faulty control board-

Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Low Supply Voltage Fault (Low input voltage):

Power supply voltage is too low-

Verify the unit is connected to 240 VAC. Heat pump operating voltage range is 204-264 VAC. The compressor will not operate below 204 VAC, but the heating elements will.

If connected to 208 VAC, a buck-boost tramsformer is required to boost to 240 VAC.

High Supply Voltage Fault (High input voltage):

Power supply voltage is too high-

Verify the unit is connected to 240 VAC, unit is intended for 240 VAC connection only. If connected to higher voltage, a buck boost transformer may be required to reduce voltage. Heat pump operating voltage range is 204-264 VAC. The compressor will not operate above 264 VAC, but the heating elements will.

If connected to 208 VAC, a buck-boost transformer is required to boost to 240 VAC.

42

Page 42
Image 42
American Water Heater HPE10280H045DV, HPE10260H045DV manual Main Control Board Crystal Fault Main board failure

RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER, HPE10260H045DV, HPE10280H045DV specifications

The American Water Heater HPE10280H045DV and HPE10260H045DV are pioneering residential hybrid electric heat pump water heaters designed to deliver energy-efficient performance while meeting the hot water demands of modern households. These innovative units fuse traditional electric heating with advanced heat pump technology, allowing for significant reductions in energy consumption compared to conventional electric water heaters.

One of the primary features of these hybrid models is their outstanding energy efficiency ratings. Both units typically achieve an impressive Energy Factor (EF) that reflects their ability to convert electricity into hot water. By utilizing ambient air to heat water, these heat pump water heaters pull in heat from the surrounding environment and transfer it to the water, thus consuming less electricity. This technology not only reduces energy bills but also decreases the overall carbon footprint of the home.

The HPE10280H045DV and HPE10260H045DV boast a sleek, compact design that allows for flexible installation options, making them suitable for various locations within a home. Their user-friendly digital interface provides homeowners with intuitive controls to manage temperature settings and monitor performance. These models are equipped with smart technology that includes an intuitive display for adjusting modes and settings. They feature selectable operating modes, including electric, heat pump, and hybrid, allowing users to choose the most efficient heating method based on current needs.

In terms of capacity, the HPE10280H045DV offers a substantial 80-gallon tank, while the HPE10260H045DV provides a 60-gallon capacity, ensuring that households of different sizes can enjoy ample hot water for showers, laundry, and dishwashing simultaneously. Both models are designed with durability in mind, featuring robust components and corrosion-resistant tanks that promise longevity and maintenance-free operations.

Another significant aspect of these hybrid water heaters is their whisper-quiet operation, which makes them ideal for installation in living spaces or areas close to bedrooms. The noise level is minimized by the efficient insulation and placement of the compressor, ensuring that the serenity of the home is maintained.

In summary, the American Water Heater HPE10280H045DV and HPE10260H045DV represent a leap forward in the water heating industry, combining innovative heat pump technology with user-friendly features, energy efficiency, and ample capacity, making them an excellent choice for environmentally conscious homeowners looking for reliable hot water solutions.