ViewStat Installation and Wiring
25
ViewStat Communicating Thermostat
6. After the address has been selected, press the Enter button to store the address.
7. Use the Scroll Up and Scroll Down buttons to set the "Number of Stats on the Network" to the highest
address that will be on the thermostat network. This will be equal to the total number of thermostats on
the network (unless one or more addresses are skipped - see step 5).
8. Press Enter to set the baud rate. The ViewStat must be set for 9600 baud to communicate with the
miniverter. This is the default setting, and you shouldn’t ever change this setting.
9. Press Enter to "Exit" the Communications Set Up sub-menu. This will return you to the main menu.
10. Press the Scroll Down button until "Exit" is displayed. Press the Enter button. The thermostat will then
reset and return to normal operation.
FIG. 17 Setting the thermostat address
Network Address
Communications
Set Up More
Set Thermostat
Address
EXIT
Back
1 to 64
Next
No.of T-stats On
the Network
Set Baud
Rate More
Select
9600
Write down the address for each thermostat.
This number must be set the same at each thermostat.