Set Up and Configuration

Communications Set-Up

This is where the thermostat address is entered. Additionally, the total number of thermostats (or the highest addressed stat on the network) is entered here to optimize communication timing. Consult a qualified service technician before changing any of the values in this Sub-Menu (Sub-Menu not shown).

Temperature Set-Up

The first and second stage differentials can be changed, as can the display temperature offset. The differentials set the tightness of the temperature control. If the equipment is operating too often, or the temperature swings are uncomfortably large, the differentials can be increased or decreased respectively. The temperature offset (calibration) allows the user to “customize” the temperature shown on the display. Consult a qualified HVAC service technician before changing any of the values in this Sub-Menu (Sub-Menu not shown).

Temperature Control Options

OFFSET

Allows the user to offset the displayed room temperature ±3°F from true tem-

 

perature. This thermostat is calibrated to be within ±1°F of true temperature.

 

 

1ST STAGE DIFFERENTIAL

Determines the level of control and consequently the cycle rate. Adjustable

 

between 0.5°F and 2.0°F, this is the value above/below the set point that the

 

temperature must rise (fall) to start the cooling (heating). It is also the value

 

below (above) the set point that the temperature must fall (rise) for the cooling

 

(heating) to stop. For example, if the temperature setting was 70°F and the 1st

 

stage differential was set at 0.5°F, in the heat mode the heat would come on at

 

69.5°F and stay until the temperature was 70.5°F. A small differential will result

 

in a tighter control, but more heating/cooling cycles.

 

 

2ND STAGE DIFFERENTIAL

Again adjustable between 0.5°F and 2.0°F, this also determines the level of

 

control by determining when to use the 2nd stage of heating or cooling. It can

 

also be used to keep 2nd stage cooling from coming on too soon when 1st

 

stage is acting to control temperature levels or to keep costly auxiliary heat

 

from coming on too soon when the heat pump is sufficient.

 

 

Backlighting Set-Up

Both displays have backlighting which can be controlled in three ways (FIG. 37). First, backlighting can be turned on every time a button is pushed. Second, it can be configured to come on with a button push, but only when the ambient light is below a preset value. When “only when needed” is selected, the user can select from two levels of ambient light. Finally, it can be disabled.

42

ViewStat Communicating Thermostat

Page 48
Image 48
AMX ViewStat manual Communications Set-Up, Temperature Set-Up, Backlighting Set-Up, Temperature Control Options

ViewStat specifications

AMX ViewStat is a revolutionary thermostat solution designed for both residential and commercial environments, providing robust control over heating, ventilation, and air conditioning (HVAC) systems. This intelligent device stands out for its user-friendly interface, advanced technology integration, and versatility in various settings.

One of the main features of AMX ViewStat is its intuitive touch screen interface, which enables users to easily navigate through settings and preferences. This 4.3-inch color display not only enhances usability but also allows for customization, offering users the ability to personalize the user experience according to their lifestyle and preferences. Whether adjusting temperature settings or scheduling heating/cooling cycles, the interface ensures a seamless interaction.

Among its key technological advancements is the integration of Wi-Fi connectivity. By connecting to a home or building's network, users can remotely access and control the thermostat through a smartphone, tablet, or computer. This level of control facilitates energy savings, as users can monitor and adjust settings from anywhere, leading to optimized usage and reduced utility bills.

AMX ViewStat is compatible with various HVAC systems, accommodating both conventional and heat pump setups. Its flexibility in adapting to different configurations makes it suitable for diverse applications, from single-family homes to large commercial spaces.

Moreover, the device incorporates advanced energy management features, granting users insights into their energy usage patterns. This data-driven approach allows users to make informed decisions about their energy consumption, ultimately promoting a more sustainable lifestyle.

In addition to its primary functions, AMX ViewStat integrates with other AMX control solutions, enabling a centralized command for home or office automation. When combined with AMX automation systems, users can achieve a fully integrated environment where lighting, security, and entertainment systems work in harmony with heating and cooling controls.

The construction of AMX ViewStat is robust yet stylish, designed to fit seamlessly into any decor. Available in multiple finishes, it adds a touch of elegance while ensuring durability and functionality.

In conclusion, AMX ViewStat is a state-of-the-art thermostat solution that offers a blend of advanced technology, ease of use, and energy efficiency. With features like remote connectivity, compatibility with various HVAC types, and integration with broader automation systems, it stands as a comprehensive solution for modern living and working environments.