Using the NetLinx Module to Program the ViewStat
49
ViewStat Communicating Thermostat
Command Interface - SEND_COMMANDs (Cont.)
Command Description
'T-<stat> HMODE?' Query for current humidify mode.
Parameter:
• <tstat> : id of thermostat/zone
Example:
'T-22 HMODE?'
'T-<tstat> HOLD-<val>' Set thermostat hold state.
Parameters:
• <tstat> : id of thermostat/zone
•<val>:
0 = take thermostat out of hold mode
1 = place thermostat in hold mode
T = toggle hold state
Example:
'T-2 HOLD-ON'
'T-<stat> HOLD?' Query for current hold state.
Parameter:
• <tstat> : id of thermostat/zone
Example:
'T-1 HOLD?'
'T-<tstat> HUMIDIFY-<val>' Set humidify set point.
Parameters:
• <tstat> : id of thermostat/zone
•<val>:
+ = Increase humidify set point by one percent
- = Decrease heat set point by one percent
10-90 = humidify point (in percent)
Example:
'T-6 HUMIDIFY-30'
'T-<stat> HUMIDIFY?' Query for current humidify set point.
Parameter:
• <tstat> : id of thermostat/zone
Example:
'T-1 HUMIDIFY?'
'T-<tstat> HUM?' Query for current inside humidity.
Parameter:
• <tstat> : id of thermostat/zone
Example:
'T-14 HUM?'
'T-<tstat> ID?' Get thermostat identification number.