Install the RapidRails slide assemblies

1.At the front of the rack cabinet, position one of the RapidRails slide assemblies so that its mounting-bracket flange fits in one U-space in the rack. The top mounting hook on the slide assembly’s front mounting bracket flange should enter the top hole of the U-space.

2.Push the slide assembly forward until the top mounting hook enters the top square hole of the U- space, and then push down on the mounting-bracket flange until the mounting hooks seat in the square holes and the push button pops out and clicks (see below).

Slide assembly (2)

Mounting bracket flange

Mounting hooks (2) Push button

3.At the back of the enclosure, pull back on the mounting-bracket flange until the top mounting hook is in the top square hole of the U-space you selected, and then push down on the flange until the mounting hooks seat in the square holes and the push button pops out and clicks.

4.Repeat steps 1 through 3 for the slide assembly on the other side of the rack.

Caution: Ensure that the slide assemblies are mounted at the same position on the vertical rails on each side of the rack.