Troubleshooting

Specifications

Input Voltage 230 Vac nominal
Frequency 45-65 Hz
Brownout Transfer 160 ±8% VAC, typical
Over-voltage Transfer 280 VAC, typical
Output UPS Capacity (total) 500 VA / 300 W
Voltage On Battery 230 Vac rms
(step-approximated sine wave)
Frequency - On Battery 50 Hz ±1 Hz, 60 Hz ±1 Hz
Transfer Time 50 Hz: 6ms typical, 10ms maximum
60 Hz: 5ms typical, 8ms maximum
Protection and
Filter AC Surge Protection Full time, 273 joules
AC Input Re-settable circuit breaker
Battery Type Maintenance free
Average Life 2 - 5 years depending on the number of discharge cycles and
environmental temperature
Typical Recharge Time 10 Hours
Physical Net Weight 5.4 kg
Dimensions (H x W x D) 18.55 cm (H) x 11.5 cm (W) x 21.3 cm (D)
Operating Temperature 0 oC to 40 oC (32 oF to 104 oF)
Storage Temperature -15 oC to 45 oC (5 oF to 113 oF)
Operating Relative
Humidity 0 to 95% non-condensing
Operating Elevation 0 to 3000 m (0 to 10,000 ft)

Service

Please DO NOT RETURN Back-UPS to the place of purchase under any circumstances.
1. Consult the Troubleshooting section to eliminate c omm on pro blems .
2. If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below.
3. Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit).
4. Be prepared to troubleshoot the probl em over the telephone with a Technical Support Repres entative. If this is not successful, the representative will issue a Return
Material Authorization Number (RMA#) and a shipping address.
5. Pack the unit in its original packaging. If the original packaging is not a vai la ble , as k APC Technical Support about obtaining a new set. Pack the uni t pro perl y to avo id
damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is
recommended).
6. Write the RMA# on the outside of the package.
7. Return the unit by insured carrier to the address given to you by APC Technical Support.

APC Worldwide Customer Support

Technical Support http://www.apc.com/support
Internet http://www.apc.com
Worldwi de +1 800 555 2725
Problem Probable Cause Solution
Back-UPS will not turn on. Circuit Breaker has tripped. Reduce the amount of equipment plugged into the “Battery Backup + Surge Protection”
outlets. Reset the circuit breaker by pushing it back in.
Utility power is not available at the wall
outlet. Ensure the fuse or circuit breaker for the wall outlet is okay, and the wall switch controlling
the wall outlet (if any) is in the ON position.
Connected equipment loses
power. The Back-UPS is overloaded. Ensure the equipment plugged into the outlets of the unit are not overloading the capacity
of the unit. Try disconnecting some of the equipment one device at a time, and see if the
problem continues.
The Back-UPS has exhausted its available
battery power. The unit can only operate on battery power for a limited amount of time. The unit will
eventually turn off when the available battery power has been used. Allow the unit to
recharge for 10 hours before continuing to use the unit.
The equipment connected to the Back-UPS
does not accept the step-approximated sine
waveform from the unit.
The output waveform is designed for compu ters and computer-related equipment. It is not
designed for use with motor-type equipment.
The Back-UPS may require service. Contact APC Technical Support for further troubleshooting.
The ON/OFF button is lit, and
the unit is beeping four times
every 30 seconds, or it is
emitting a constant tone.
The unit is using battery. The unit is operating normally and using battery power. Save any current work, turn off all
equipment, and turn the unit OFF. Once normal power is restored, turn the unit back ON,
and turn on all equipment.
The On/Off button flashes once
per second, and the Back-UPS
beeps once per second at the
same time.
Battery capacity is low (there is about 2
minutes of use remaining). The unit is about to shut down due to a low battery charge condition! When the unit beeps
once every second, the battery has about 2 minutes of power remaining. Immediately
power down your computer, and turn the unit OFF. When power returns to normal, the unit
will recharge the battery.
Inadequate runtime. The battery is not fully charged. Allow the unit to charge by leavi ng it plugg ed in, and switc hed on for 10 hours .
The battery is near the end of useful life. As a battery ages, the amount of runtime available will decrease. Batteries also age
prematurely if the unit is placed near excessive heat. If the battery will not charge, the
Back-UPS is no longer operable.

Battery Replacement

The battery in the Back-UPS 500 is not user-replace-
able. Contact APC Sales and Technical Support f or a
list of authorized service centers near you.

Warr anty

The standard warranty is 2 years from the date of
purchase. The APC standard procedure is to replace the
original unit with a factory reconditione d unit. APC will
ship the replacement unit once the defective unit is
received by the repair department or c ross-ship upon the
provision of a valid credit card number. The customer
pays for shipping to APC, and APC pays ground freight
transportation costs back to the customer. Customers
who must have the original unit back due to assigned
asset tags and set depreciation schedules must declare
such a need at first contact with APC Technical Sup port .
Indonesia 0800 1088 088
Malaysia 1800 80 1030
Philippines 1800 1651 0302
Singapore +65 6389 6823
Thailand 001 800 65 6340
Vietnam (1201 0288) 1 888 576 6432