Irrigation, Rainwater Runoff, and Landscape Features:
Place the heat pump away from direct rain runoff from roofs. A gutter or rain shield may be required on the roof edge above the heat pump. Relocate or adjust irrigation to avoid water spray directly onto the heat pump. Do not locate the heat pump directly adjacent to plants, shrubs, or bushes. Doing so will prevent proper air circulation into the unit, and may inhibit access to the heater when service is needed. Consult drawings on previous page (Recommended Installation Clearances) for proper spacing to other objects.
Equipment Pad Requirements:
The equipment pad should be constructed of concrete, pressure treated wood, or other material intended for the use. The pad shall be elevated and placed to provide adequate drainage and support to the base of the heat pump. The pad should be essentially level with just enough pitch to drain condensate and any other water away from the heater. In addition, the pad shall
Anchoring Heater to Pad:
Follow all relevant local, state, or national requirements regarding wind load anchoring. When anchoring is required, useAquaCal optional Hurricane Anchoring Kit, PN: STK0001. AquaCal anchoring kits satisfy, completely, the very stringent Florida Building Code Section 301.13 wind anchoring requirements. As necessary, contact AquaCal Technical Support
Overview:
When planning plumbing system layout, reference the plumbing schematics following this section as a guide to the sequence of equipment, valves, fittings, etc. The plumbing configurations for typical installations are diagrammed. In operation, it is imperative the heat pump receive water flow within the
Parts and Materials:
Industry technology changes much too rapidly for AquaCal to specify, with exactness, any items outside and beyond the heat pump. What is specified is that the heater must be installed in accordance with all applicable local, state, or national codes & standards.
Water Connections to Heat Pump:
All Heat Wave and AeroTemp heat pumps are supplied with 2" PVC plumbing unions. Connection to site plumbing is made via PVC solvent cement to the female slip socket of the plumbing unions.
Maintain Ability to Winterize:
In regions where hard winters are typical, the unions mentioned above allow for easy disconnection/reconnection of the heater from/to the plumbing system. Caution: Do not defeat the function of the
Maximum Operating Pressure: 50 PSI
Minimum/Maximum Water Flow Rates:
All Heat Wave andAeroTemp models are designed to operate successfully between flow rates of