INSTALLATION
Placement of Heater
Indoor Installation
Indoor installations can be problematic, and for that reason are discouraged. However, if no viable alternative exists, indoor installations may be successfully accomplished provided very exacting criteria is addressed. Every indoor installation is unique; therefore, there are no specific guidelines for this type of installation. If considering an indoor installation, you are strongly urged to contact AquaCal Engineering or Technical departments
Outdoor Installation
Service and Operational Clearances:
♦To operate correctly, heat pumps require large volumes of air moving over the heat collector. Allow adequate clearance between the heat pump and walls, fences, shrubs, or other objects. Refer to recommended clearance drawings below.
♦Allow five (5) feet of vertical clearance between the top of the heat pump and any roof overhang or other obstruction. This clearance prevents cold discharge air from recirculating back into the heat pump (recirculation would reduce the overall performance of the heat pump).
♦The access panel requires removal during installation and service. Do not place plumbing, or other items, closer than 30” from the front of the heater.
Code Required Clearances:
In addition to the previously stated clearance requirements, follow all applicable local, state, and national requirements relative to spacing from other objects or equipment.
Typical Installation Clearances
OVERHANG
WITH
GUTTER
RAIN RUN-
OFF MUST BE
DIRECTED
AWAY FROM
UNIT.
30” MINIMUM
CLEARANCE,
FRONT
5 FT. MINIMUM
CLEARANCE,
OVERHEAD
1FT. MINIMUM CLEARANCE,
REAR
(REAR)
24- |
|
| |
24- | |||
INCHES |
| ||
| INCHES | ||
(SIDE) |
| ||
| (SIDE) | ||
|
| ||
|
|
| |
|
|
|
(FRONT)
12