GASEOUS FUEL INFORMATION

INCORRECT INSTALLATION OF THIS GENERATOR SET COULD RESULT

IN PROPERTY DAMAGE, INJURY, OR DEATH! INSTALLATION OF THIS

GENERATOR SET MUST BE PERFORMED BY A QUALIFIED,

PROFESSIONAL TECHNICIAN OR CONTRACTOR.

THIS INFORMATION IS FOR GENERAL REFERENCE ONLY! IT MUST NOT BE USED AS THE SINGLE SOURCE OF INFORMATION FOR INSTALLING THE GENERATOR SET. FOR MORE SPECIFIC/DETAILED INFORMATION READ THE INSTALLATION MANUAL THAT ACCOMPANIED THE GENERATOR SET.

Before undertaking installation of gaseous fuel supply piping from a remote fuel source to the generator set, a check should be made concerning local and state regulations governing the use, application, and installation of gaseous fuel. These regulations along with the standards set forth by the NFPA (National Fire Protection Agency) should be followed for safe, dependable, and proper installation.

The applicable NFPA regulations are covered in the following NFPA Publications:

No. 37 - Combustion Engines No. 54 - Gaseous Appliances and piping No. 58 - Storage and handling LPG

These publications are available at a nominal price from:

The National Fire Protection Agency P.O. Box 9101 Quincy, MA 02269

GASEOUS FUEL SUPPLY PIPING

GASEOUS FUELS ARE HIGHLY COMBUSTIBLE AND CAN CAUSE

EXPLOSIONS, FIRE, INJURY, OR DEATH! THE FUEL SUPPLY SYSTEM MUST

ONLY BE INSTALLED AND ADJUSTED BY AN EXPERIENCE, PROFESSIONAL

TECHNICIAN USING APPROVED PIPING AND COMPONENTRY.

For the purpose of calculating piping size, the fuel consumption of an engine is figured at approximately 10,000 BTU's needed per horsepower per hour. For example, a 10 horsepower engine will require 100,000 BTU's of gaseous fuel per hour. Operating on natural gas which contains 1,000 BTU's per cubic foot, this engine would require 100 cubic feet of natural gas an hour to operate properly. In addition to fuel consumption, the following factors must be considered when installing the gaseous fuel supply piping:

1.Pressure loss due to the number of fittings (elbows, reducers, etc.).

2.Specific gravity of the gaseous fuel.

3.Pressure loss due to the length of the fuel supply piping.

The accompanying gas flow/pipe capacity charts list the capacity of various sizes and pipe run lengths. The capacity, which is given in cubic feet per hour, is calculated for both propane and