STANDBY PERMANENT - MOUNT SERIES GENERATOR

ELECTRICAL CONNECTION INFORMATION

High voltage may be present at receptacles and load studs while engine is operating - DANGER of electrical shock is present. Use extreme care.

Voltage is present at the 120V/15 Amp convenience receptacle only when generator is operating.

When configured for 277/480 main output, these receptacles Will be delivering 139 VAC. Disconnection to avoid possible equipment damage is suggested.

HARD WIRE LOAD TERMINAL BLOCK

1.Voltage available at load block is outlined in a chart below.

2.Cables must be brought into load block cabinet.

3.Do not start engine with load turned "on". Allow engine to come up to speed and warm up first.

 

AVAILABLE VOLTAGE:

CONNECTION OF

 

GENERATOR LEADS

STUD

120/240

4 LEAD

1-2 = 240 VAC, 1 Phase

 

 

1-N, 2-N = 120 VAC, 1 Phase

277/480

High Wye

1-2-3 = 480 VAC, 3 Phase

 

 

1-N, 2-N, 3-N = 277 VAC, 1 Phase

120/240

Delta

1-2-3 = 240 VAC, 3 Phase

 

 

2-3 = 240 VAC, 1 Phase

 

 

1-N, 2-N, 3-N = 120 VAC, 1 Phase

120/208

Low Wye

1-2-3 = 208 VAC, 3 phase

 

 

2-3 = 208 VAC, 1 Phase

 

 

1-N, 2-N, 3-N = 120 VAC, 1 Phase

 

 

 

Page 20
Image 20
Baldor ISO9001 manual Electrical Connection Information, Hard Wire Load Terminal Block