TROUBLESHOOTING - GENERATOR

As with any machine, trouble may develop in electrical generators. It may be due to long service or neglect of regular maintenance. Servicing, and checking. Should trouble develop, the following instructions will be helpful in tracing the cause and making repairs.

SPEED DEVITIONS:

The generator speed should be maintained at rated nameplate speed. The frequency and voltage of the generator output depends on speed. If the generator runs slower than rated speed, the voltage will drop off.

 

NO VOLTAGE

CAUSE

CHECK AND REMEDY

Loss of residual magnetism in

Flash Field.

exciter field poles.

 

Open in stator windings

Check for continuity in windings. Return to factory for

 

repair if open

Open or short in rotating rectifiers.

Check rectifiers.

Short Circuited.

Clear lead to restore voltage build-up.

Open in alternator field

Check for continuity and return rotor to factory for

 

repair if field coils are open.

Shorted exciter armature

Check for short and replace if faulty.

Shorted leads between exciter

Test and repair

armature and generator field.

 

 

LOW VOLTAGE

CAUSE

CHECK AND REMEDY

Excessive load.

Reduce load. With 3 phase generators, the load on

 

each leg should be as evenly balanced as possible

 

and should not exceed the rated current on any leg.

Low Speed.

Check engine for malfunction or system for overload.

Line loss.

Increase size of line lead wire.

Page 37
Image 37
Baldor ISO9001 manual No Voltage, LOW Voltage