CRANKING CONTROL

3. Overspeed Adjustment (OS) - Over Frequency

Overspeed protection is provided by a frequency sensing network within the controller. The trip point of the frequency network is adjustable via a rheostat located on the top of the controller at

the right hand side. Clockwise (CW) rotation increases the trip frequency and, thereby, raises the shutdown speed.

CRANKING CONTROL

1. Overcrank Protection

This feature provides a preset second crank cycle. Failure of the engine to start by the end of the crank period results in an "overcrank" shutdown and alarm indication.

2. Cranking Disconnect Adjustment (CDS Adjustment)

The cranking disconnect signal is obtained by a frequency network within the controller. The trip point of the frequency network is not adjustable.

LOSS OF FREQUENCY

Internal protection against loss of frequency input to the cranking disconnect circuit is programmed in after the unit has started normally. In the event the frequency goes to zero (engine runs out of fuel, frequency signal source fails, etc.) the LOP shutdown circuit is bypassed and a 12-second wait period is initiated. If frequency returns within this time period, LOP monitoring resumes and operation continues normally. If frequency has not returned at the end of this time period, the engine oil pressure status is observed to determine whether the engine is actually running or stopped. If the engine has stopped (i.e. air in fuel, etc.) the cranking cycle will begin in an effort to restart the engine. If the engine has not stopped (loss of input signal, etc.) the unit is shut down with an "overcrank" indication and alarm.

"Overcrank" indication can mean a loss of crank-disconnect signal during the previous run period. Attempting to restart the engine with no crank- disconnect can destroy the starter motor, which can cause serious personal injury.

This is of particular note since the tendency is to pursue only cranking and start related faults. The cranking disconnect signal source is a key component in this system and must be checked out thoroughly whenever an "overcrank" shutdown occurs.

The controller does not provide protection against loss of signal during startup. A shutdown with alarm, due to any of the above conditions, will prevent any subsequent operation of the generator set. The run-stop-auto selector switch on the control panel must be momentarily placed in the "stop" position to reset these functions.

If a dead battery is suspected, remove controller fuse, Replace with new battery and attempt starting. Damage to engine control may result from jump- starting.