7.0 Site Requirement
Termination via internal discharge branch e.g sink waste - downstream
Direct Connect Fitting | Pipe must terminate | ||||||||||
|
|
|
|
|
|
|
|
|
| above water level but | |
|
|
|
|
|
|
|
|
|
| below surrounding surface | |
| Sink |
|
| ||||||||
|
|
| |||||||||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10° 10°
Branch of Tee to be
± 10° from vertical
7.7 | Condensate Disposal (cont.) | |
9. Ensure that the condensate can discharge freely (without | ||
blockage or restriction of the pipe) into the drain. | ||
10. Examples are shown of condensate pipe methods of | ||
termination:- |
| |
| i) | via an internal discharge branch |
|
| (e.g. sink waste) - Fig. C. |
| ii) | to an internal or external soil and vent pipe - |
Fig. C
From Boiler
| Fig. D. |
iii) | to a drain or gully - Fig. E. Ensure that the |
| condensate can discharge freely (without |
| blockage or restriction of the pipe) into the |
| drain. |
iv) | to a soakaway - Fig. F. |
|
|
Termination to an internal soil and vent pipe
Direct Connect Fitting |
From Boiler |
Min. 450mm![](/images/new-backgrounds/1055784/5578435xi2.webp)
Fig. D
Termination to a drain or gully
From Boiler
Fig. E
Pipe must terminate above water level but below surrounding surface
Termination to a purpose made
|
|
|
|
|
|
|
|
|
| 500mm Min |
|
|
|
|
|
|
|
|
|
| |
From Boiler |
|
|
|
|
|
|
|
|
| Holes in the |
|
|
|
|
|
|
|
|
|
| face away from the building |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. F
18© Baxi Heating UK Ltd 2011