Baxi Potterton Gold FSB 30 HE manual System Controls & Wiring

Models: Gold FSB 30 HE

1 60
Download 60 pages 23.16 Kb
Page 13
Image 13

Key to colours

b- Blue br - Brown

w - White

o- Orange

gr - Grey

g/y - Green/Yellow

230V

 

 

 

50Hz

 

 

Y Plan

L N E

b

 

 

g/y

w

Diverter

 

 

 

 

Cylinder

Valve

 

 

Stat

gr

 

Room

1

o

 

 

 

 

 

 

Stat

C 2

 

 

 

 

System Control

 

S/L

E

N

P/L

 

 

 

 

Boiler Connection

Wiring Centre

 

 

 

 

 

 

 

 

(4 Core Wire)

 

 

 

 

 

Timer

 

 

 

 

 

L

 

 

 

 

 

N

N E

L

 

 

 

CH on

 

 

 

HW on

 

 

 

 

 

HW off

Pump

 

 

 

Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat, DHW Interlocked By Cylinder Thermostat

At least the Radiator(s) near the Room Thermostat not TRV’d

Pump run from Switched Live

6.0System Details

6.6System Controls & Wiring

This boiler requires a permanent live for operation of the condensate pump and frost protection.

1.To comply with Part L1 of the Building Regulations the heating system into which the boiler is installed should include the following:

a)zone controls

b)timing controls

c)boiler control interlocks

2.Such a system needs to be fully pumped and must provide independent temperature and time control to both the heating and hot water circuits and have a boiler and system pump interlock.

3.The boiler should be controlled so that it operates on demand only. Where it is proposed to effect control by thermostatic radiator valves a room thermostat should also be provided to switch off the boiler when there is no demand for heating.

230V

50Hz

L N E

System Control

Wiring Centre

Timer

L

N

CH on

HW on

 

 

b

gr

gr

 

 

 

 

 

b

Motor

 

Motor

 

 

br

 

 

 

br

S Plan

o

g/y S Plan

g/y

Valve

 

Valve

 

Room

Cylinder

o

 

Stat

Stat

 

S/L E N P/L

Boiler Connection

(4 Core Wire)

N E L

Pump

S Plan, Room Thermostat System, CH Interlocked By Room Thermostat, DHW Interlocked By Cylinder Thermostat

At least the Radiator(s) near the Room Thermostat not TRV’d Pump run from Switched Live

© Baxi Heating UK Ltd 2011

13

Page 13
Image 13
Baxi Potterton Gold FSB 30 HE manual System Controls & Wiring