Baxi Potterton Gold FSB 30 HE manual Plume Displacement Kit P.D.K

Models: Gold FSB 30 HE

1 60
Download 60 pages 23.16 Kb
Page 25
Image 25

Plume Outlet (‘Peak’

MUST be Uppermost)

0.94 metre

Fig. C

9.0Plume Displacement

9.1Plume Displacement Kit (P.D.K.)

Kit No 5121371

Content of kit

1 70/110 Concentric Flue

11m 70 Dia Exhaust Flue Pipe

2Support Brackets

193° Elbow/Plume Outlet Assembly

1Flue Trim

2“O” Rings

1Elbow with Gasket

1.This kit is recommended for installations where the condensate plume emitted from the flue may cause a nuisance or affect the surroundings.

2.The terminal must be positioned outside the building with the outlet connection upwards.

3.The 70Ø pipe connects to the outlet of the concentric terminal assembly. The elbow/plume outlet must be fitted to the end of the 70Ø pipe.

NOTE: The plume outlet must always be at least 45° to the wall, with the ‘peak’ uppermost to prevent rain entry (Figs. A & B), and be at least 2 metres above ground level. It must be secured as shown in Fig. C.

The outlet must be positioned so that any condensate plume is directed away from adjacent surfaces.

4.

It is possible to reduce or increase (with the addition of

extensions) the length of either or both the 70/110 concentric

and 70Ø exhaust.

5.

Standard concentric flue extension kits may be added

 

45°

Outlet must be

 

at least 45° from

45°

 

 

wall face

Fig. A

‘Peak’ MUST be Uppermost

500mm Min.

between the boiler elbow and the terminal assembly.

6. The minimum length of the concentric flue is 100mm when

measured from the edge of the boiler flue elbow. There is a

further 45mm engagement into the elbow.

IMPORTANT: The maximum equivalent length of

concentric flue is:- 4 metres

Additional elbows may be fitted in the concentric flue, but the equivalent length must be reduced by 1 metre (93° elbow) or 0.5 metres (45° elbow).

7.70Ø 1 metre extensions (including support bracket), and additional 93° & 45° elbows are available. Any additional 93° & 45° elbows must be accounted for when calculating flue lengths. 70Ø 93° elbows are equivalent to 3.5 metres of straight length and 45° elbows to 1 metre.

NOTE: Permitted positions of the plume outlet relative to doors, windows etc. are the same as for conventional concentric flues as detailed in the main Installation &

Outlet Connection upwards

Fig. B

Servicing Instructions and BS5440 Pt. 1. It is NOT necessary to fit a terminal guard over the air inlet or the plume outlet.